Dimensions

Radio or LAN: 70 mm (h) x 125mm (w) x 16mm (d)

Dual Radio: 70 mm (h) x 125mm (w) x 21mm (d)

Dual LAN: 70mm (h) x 125mm (w) x 23mm (d)

Weight TBC
Temperature -10 °C to + 55 °C
Humidity 0 - 90% non-condensing
Mounting TBC
Warranty 5 years
Power Requirement

10 - 30 Volts DC

In order to maintain compliance with requirements for electrical safety the Dualcom Pro should always be powered from a fused supply with following rating:

  • For a 12V DC system (supply voltage in the range 10 Volts DC to 14 Volts DC) a fuse rated at 1.25
  • For a 24V DC system (supply voltage in the range 20 Volts DC to 30 Volts DC) a fuse rated at 600 mA

If the power source is not limited to these values, then a fuse with the correct rating must be fitted in line with the positive connection from the power source.

The SPT will shut down on detecting a low supply of 7.6 Volts DC +/- 0.5 Volts DC

Current Consumption TBC
Radio Path 2G, 3G, 4G
Output Ratings Maximum applied voltage = 60V
Maximum current = 150mA
Aerial 50 ohms (nominal) on MMCX socket
Operation Method Pass Through
CIE Interconnections Input triggering (standardised parallel), Dial Capture, RS232, RS485, TTL, Ethernet
RCT Protocols SIA
Input Terminals Max +30v, Min 0 volts DC (reference supply 0v supply) 100k
User Serviceable Parts There are no serviceable parts within the DualCom Pro Range
Environmental Class II
Applicable Standards

Suitable for use in alarm systems complying to:

  • EN50131-1:2006+A2:2017
  • EN50136-1:2012+A1:2018
  • PD6662:2017
  • PD6669:2017

Emissions Standard

  • Radio Equipment Directive 2014/53/EU (RED)

Environmental Standard

  • EN 50130-5 Environmental Class II

ATS Configuration EN 50131-10:2014 Type Y

ATS Classification EN 50136-2:2013 SP2, SP3, SP4
ATS Classification EN 50136-1-1:1998

  • Radio D3, M3, T4, S2, I3, A4 (ATS5)
  • LAN D3, M3, T4, S2, I3, A4 (ATS5)



DualCom Pro 4

DigiAir Pro 4

PATH AVAILABLE GRADES WHAT'S IN THE BOX PART NUMBER
Radio SP2 DigiAir Pro 4, serial cable & small aerial CS.51.R2
LAN SP2 DigiAir Pro 4, serial cable, ethernet cable CS.51.L2


GradeShift Pro 4

PATH AVAILABLE GRADES WHAT'S IN THE BOX PART NUMBER
LAN + Radio DP2, DP2+, DP3, DP4 GradeShift Pro 4, serial cable, aerial and ethernet cable

CS.53.LR2

CS.53.LR2P

CS.53.LR3

CS.53.LR4

Radio + Radio DP2, DP2+, DP3 GradeShift Pro 4, serial cable, 2 x aerial

CS.53.RR2

CS.53.RR2P

CS.53.RR3



25
DualCom Pro 4

CSL DualCom ltd.

Building 4, Croxley Park, Hatters Lane, Watford, WD18 8YF

EN 54-21:2006

Fire detection and fire alarm systems / Alarm transmission and fault warning routing equipment

 EN 50131-10:2014

EN 50136-1:2012/A1:2018

EN 50136-2:2013

PD6662:2017 / PD6669:2017

Type of transmission system: Type 1

SP5 / DP4

Security Grade:1-4 depending on the I&HAS housing in which it is installed.

Environmental Class: II