Panel Connection – RS232
Manufacturer | TYCO |
Model | MZX and MX |
Cable Required | Unterminated serial cable with RJ11 connector |
Panel Profile | TYCO-MX-PRINTER-SIA-RS232 or TYCO-MX-UDL-RS232 |
Pannel Connection | RS232 |
Technical Notes |
Only one of Alarms and UDL can be used. Select the appropriate Panel Profile during configuration based on the panel setup. Use the panel’s printer port to connect to the DualCom Pro for Alarms. If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
Panel Connection Information
DualCom Pro | COM 1 Printer RJ11 | COM2 PC RJ11 |
RTN | Pin 1 (GND) | Pin 1 (GND) |
RS232-T | Pin 2 | Pin 2 |
RS232-R | Pin 3 | Pin 3 |