Panel Connection – Dial Capture
Manufacturer | Risco |
Model | Gardtec 600 Series |
Version | N/A |
Minimum Panel Firmware | N/A |
Cable required? |
MCM connected to
|
Panel Profile | GARDTEC-MCM |
Panel Connection | Dial Capture |
Technical Notes |
Only SIA is supported. If Fast Format is required use GENERIC-ALARMS-MCM as Panel Profile. |
DualCom Pro to Panel Wiring
DualCom Pro 1 - MCM plug-on module - Line A DualCom Pro 2 - DI |
PSTN A |
DualCom Pro 1 - MCM plug-on module - Line B DualCom Pro 2 - AL |
PSTN B |
Panel Config
Set up Alarm Format:
- Enter Keypad Access Code to get into Engineer mode (Default is 1234) followed by [YES]
- Press [3] [4] [YES] to jump to Digicom
- Press [NO] until you see ‘Mod + SIA’
- Press [YES]
- Press [0]
- Press [NO] until you see ‘Program Digicom Type or Test?’
- Press [NO] until you see ‘Program Digicom Functions?’
- Press [YES] [YES] (To change channels/triggers)
- Press [NO] once
- Press [YES] until the “>” appears next to PA
- Press [NO] to change the ‘Off’ to ‘On’
- Press [YES] [YES]
- Press [0] repeatedly to get out of Engineer mode
Set up Communication and line monitor security:
- Enter Keypad Access Code to get into Engineer mode (Default is 1234) followed by [YES]
- Press [3] [4] [YES] to jump to Digicom
- Press [0] (go back)
- Press [NO] until you see ‘Functions’
- Press [YES]
- Press [NO] until you see ‘Comms Functions’
- Press [YES]
- Press [NO] until you see‘Comms=On’
- Press [YES]
- Press [NO] and key in the required Site Code/Id
- Press [YES]
- Press [NO] and key in the required ARC telephone number
- Press [YES]
- Press [YES] till you see 'Line Monitor'
- Press [NO] till you see 'Line Volts'
- Press [YES]
- Press [[NO] till you see 'Line Security'
- Press [NO]until ‘Low’ to set Line Monitor to low security
- Press [YES]
- Press [0] multiple times to get out of engineer mode