Panel Connection – RS232

Manufacturer Kentec
Model Syncro and Solo series
Version
Minimum Panel Firmware
Cable Required? A dual row, 10-way terminal housing with 2.54mm pitch with pins 1, 5 and 7 wired
Panel Profile KENTEC-FIRE-RS232
Panel Connection RS232
Technical Notes

The panel profile defaults to EN54 Fire Mode.
Please contact Tech Support if you require to configure the panel in non-Fire mode.

If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide.

DualCom Pro to Panel Wiring

RS232-T Pin 1
RS232-R Pin 7
RTN Pin 5

Panel Setup

The SPT expects the panel address to be 1. This can be viewed using the panel manufacturer’s software and ensuring the node address is set to 1 in the Configure Node window.