Panel Connection – RS232
Manufacturer | Honeywell |
Model | Notifier |
Series | ID2000 |
Cable Required | Unterminated serial cable with 9 Way D-Type IDC socket |
Panel Profile | NOTIFIER-PRINTER-RS232 |
Panel Connection | RS232 |
Technical Notes |
ID3000 is not supported If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
Panel Connection Information
RS232-T | 9 Way D-Type Pin 2 |
RS232-R | 9 Way D-Type Pin 3 |
RTN | 9 Way D-Type Pin 5 |
The non-isolated DB9 printer port should be used for connecting to the DualCom Pro.
Panel Setup
Navigate to the RS232 Port.
Set type to 3rd Party Device.
Set Baud rate to 9600.
Note:
To comply to EN54 standards, the instructions in CSL DualCom Pro 2 Fire EN54 Variant Quick Guide must also be followed.