Panel Connection – RS232
Manufacturer | Honeywell |
Model | Gent |
Version | Fire panel must be running the 3400 Basic Communications Protocol (issue 1.13 or later) |
Minimum Panel Firmware | |
Cable required? | |
Panel Profile | HONEYWELL-GENT-RS232 |
Panel Connection | RS232 |
Technical Notes |
There are 3 SIA reporting modes which provide different ways of reporting fire panel events and alarm information. The default mode 0 is recommended. If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
DualCom Pro to Panel Wiring
RS232-T | Card 0 Port 1 RX1 |
RS232-R | Card 0 Port 1 TX1 |
RTN | Card 0 Port 1 0V |
Panel Setup
Alarms should be set up on the panel for RS232 Card 0 Port 1
The port mode should be set as Universal, and the port speed (baud) should be set to 19200.
Note: If Card 0 Port 1 is being used for something else than use Card0 Port 2 instead and wire accordingly.