Panel Connection – RS232
Manufacturer | TYCO |
Model | Fireclass |
Cable Required | Unterminated serial cable with RJ11 connector |
Panel Profile | FIRECLASS-PRINTER-RS232 or FIRECLASS-UDL-RS232 |
Pannel Connection | RS232 |
Technical Notes |
Only one of Alarms and UDL can be used. Select the appropriate Panel Profile during configuration based on the panel setup. Use the panel’s printer port to connect to the DualCom Pro for Alarms.Use the panel’s local port to connect to the DualCom Pro for UDL. |
Panel Connection Information
DualCom Pro | COM 1 Printer RJ11 | COM2 PC RJ11 |
RTN | Pin 1 (GND) | Pin 1 (GND) |
RS232-T | Pin 2 | Pin 2 |
RS232-R | Pin 3 | Pin 3 |