Panel Connection – Serial RS232
Manufacturer | Pyronix |
Model | Euro |
Version | 280 |
Minimum DualCom Pro Firmware | DualCom Pro: V2.24 DualCom Pro 2: V2.0.1 |
Minimum Panel Firmware | V9.54d |
Cable required? | Use the FPRS232 module and use a standard 3 wire cable |
Panel Profile | Pyronix-Euro-RS232 |
Panel Bus Connection | RS232 |
Technical Notes | The FPRS232 module can be bought from Pyronix themselves |
Panel Connection Information
Cable | Module |
RS232-T | FPRS232 - RXD |
RS232-R | FPRS232 - TXD |
RTN | FPRS232 - GND |
Panel Programming
- Enter “Engineer Mode” > Select “Program ARC/SMS” > Select “Calls”
- Set “ARC/SMS” to “Enabled” [0] > Select “ARC Details” [1] and set “Active” to “Yes” [1] > Set
“Format” to “WebWayOne” [141] - Set “SIA Ack Char” [006] > Set “SIA Nack Char” [021] > “Valid Areas” is Engineer’s choice > “Area
Accounts” is Engineer’s choice - Set “ARC Account” to “Site ID/Account No” > Set “Content” [1-32] Engineer’s choice
- Set “Redials” [03] > “Set Time Out Seconds” [30] > Set “Test Calls” Engineer's choice
- Exit “Engineer Mode” into “Day Mode”
Remote Access Programming
- Go to ‘Set Up Downloading’ > Select “Download” by (WebWayOne) [4]
- Select “Poll Timeout” [10] > Select “Modem Init Timeout” [060]
- Select “Rings to Answer” [1] > Select “Comm Tx Timeout” [030] > Select “Comm Dial Timeout”
[030] - Select “UDL Tx Timeout” [02] > Select “ARMPC Tel No” (Leave Blank)
- Select “Program PCs” [1] > “Modem Tel No” (Leave Blank)
- Select “Signal Alarms No” [0] > Select “Signal Faults No” [0] > Select “Signal Set/Unset No” [0]
- Enter 1111
- Press YES until Program PC 1 and enter 1111 again