Panel Connection – TTL
Manufacturer | Eaton |
Model | Scantronic/Menvier |
Version | I-ON (100, 160, 300, 1000) |
Minimum Panel Firmware | MIN – V4:03 |
Cable required? | Standard alarm cable |
Panel Profile |
|
Panel Bus Connection | TTL |
Technical Notes | For SIA and UDL you will require a CS.1.403 Scantronic i-ON plug on board |
Panel Connection Information
SPT | Serial Board |
TTL-T | R |
TTL-R | T |
RTN | RTN |
Panel Programming
- To configure the panel, the DualCom Pro unit must be fully configured and wired to the panel and then
rebooted. This causes the panel to query all devices connected and make various menu options
available in the Keypad and in the Web browser - “Panel Communication” on initial setup
- If no data transfer has occurred between the DualCom Pro unit and the Scantronic i-ON after a short
period of time, the panel stops communicating and will require a restart to begin again. This
only applies to the initial setup and does not affect ongoing alarm communications - Enter “Engineer Mode” > “Installer Menu” will be displayed “Detectors/Devices” below > Press
the “Down” button until you find “Communications”> Press the “Right” button - “Communications” will be displayed with “ARC Reporting” below it > Press the “Right” button
- “ARC Reporting” will be displayed with “Call Mode” below it > press the “Right” button
- “Call Mode” will be displayed > press the “Up/Down” buttons to select “Single” > press the
“AcceptTick” button - Press the “Down” button
- “ARC Reporting” will be displayed with “IP Network” below it > press the “Right” button
- “IP Network” will be displayed with “Unit Name” below it > press the “Right” button > enter a
“Description Name” > press the “AcceptTick” button - Press the “Down” button > “Polling IP Address” will be displayed > press the “Right” button and
clear the contents > press the “AcceptTick” button - Press the “Down” button > “ARC IP Address” will be displayed, press the “Right” button” > “IP
Address 1” will be displayed - Enter IP address “127.0.0.1” > to enter a “Dot”, press the “*” button > press the “AcceptTick”
button - Change “IP Address 1” to the description name as chosen in step 7 > press the “AcceptTick”
button - Press the “Down” button and “IP Address 2” is displayed > press “Right” button” to clear contents
- Press the “AcceptTick” button” twice > press the “Left” button” twice back to “ARC Reporting”,
displayed with “IP Network” below it - Press the “Down” button” and “Account Numbers” will be displayed > press the “Right” button” >
select “Accounts” to enter account numbers - Back to “ARC Reporting” and “Account Numbers”
- “Report Type” will be displayed > press the “Right” button > select “SC SIA 3”
- CID/SIA Events > press the “Right” button > set selection
- “Restorals”, press the “Right” button > set selection
- Back to “Communications” > IP Network (Own) > press the “Right” button” > on Module:
Ethernet, press the “Right” button > Enter the following IP Address = 127.0.0.1 - IP Network (Own) > Module: Ethernet > Port Number = 55132
- IP Network (Own) > Module: Ethernet > Subnet Mask = 255.255.255.0
- IP Network (Own) > Module: Ethernet > Gateway Address = 127.0.0.1
- “Downloading” > “Account” > “Name = As per Installation”
- “Downloading” > “Account” > “Serial Number = Any 8-digit number”, must match the number
entered into the UDL software - “Downloading” > “Access Mode” = Unattended
- “Downloading” > “IP Network” > “IP Address” > “IP Address 1 = 127.0.0.1”
- “Downloading” > “IP Network” > “IP Address” > “IP Address 1”, change to description chosen
earlier - “Downloading” > “IP Network” > “IP Address” > “IP Address 2 = empty”
- “Downloading” > “IP Network” > “Port Number” > “select the descriptor chosen earlier = 55132”
- “Downloading” > “IP Network” > “Port Number” > “IP Address 2 = empty”
For panel version 4.0 firmware and above
- Login to panel as a User
- Select “System Config” > Facilities ON/OFF > set Remote Access to “ON”
- Select password (optional UDL password)
Web access – Only complete these steps if web access is needed
- If you require web access, then the panel requires a fixed IP address allocated to it
- IP Network (Own) > Panel Ethernet > Web Server > Status = Enabled
- IP Network (Own) > Panel Ethernet > Web Server > Port Number = 80
- Exit Engineering Mode and save the configuration
- IP Network (Own) > Panel Ethernet > IP Address = Allocated IP address
- IP Network (Own) > Panel Ethernet > Subnet Mask = 255.255.255.0
- IP Network (Own) > Panel Ethernet > Gateway Address = Allocated IP address
- Known Panel Issue - some panels require a timer to be adjusted to the background of the UDL
Package