Panel Connection – RS232

Manufacturer Advanced
Model MX Pro 4/5
Version -
Minimum Panel Firmware -
Cable required? Core alarm cable
Panel Profile ADVANCED-MXPRO-PRINTER
Panel Connection RS232
Technical Notes

Apollo protocol was set during testing

Any unrecognised panel event will be delivered as SIA YO unknown messages

If an EN54 compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide

DualCom Pro to Panel Wiring

RS232-T Right Pin (White)
RS232-R Left Pin (Orange)
RTN Centre Pin (Green)

Panel Setup

Setup-Printer>

Tick “External”

Tick “Fires”

Tick “Alarms”

Tick “Faults”

Tick “Tests” if you want to see alarms in Fire-Test mode.

 

Troubleshooting

The Advanced MX Pro 5 may generate earth faults. Either disable earth fault alarms on the panel or install a 24V DC Isolator Module (MXP-542) on the power inputs to the DualCom Pro.