Panel Connection – RS232
Manufacturer | Advanced |
Model | Hertek |
Version | Penta with Optional BMS Interface Module (MXP-510) |
Minimum Panel Firmware | BMS firmware V52019ar or greater |
Cable required? |
Direct wiring as shown below |
Panel Profile | PENTA-RS232 |
Panel Connection | RS232 |
Technical Notes |
The DualCom Pro can be wired to either the Panel onboard RS232 connector or the MXP-510 module RS232 when fitted. If an EN54 compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide |
Panel Connection Information
RS232-T | Panel’s RS232 RX | MXP-510 RS232 RX |
RS232-R | Panel’s RS232 TX | MXP-510 RS232 TX |
RTN | Panel’s RS232 GND | MXP-510 RS232 GND |