Panel Connection - RS232
Manufacturer | Eaton |
Model | Scantronic S95 |
Version | N/A |
Minimum Panel Firmware | V1.06 |
Cable required? | Unterminated serial cable with 9 Way D-Type IDC socket |
Panel Profile | Scantronic-S95-RS232 |
Panel Bus Connection | RS232 |
Technical Notes | See below |
Panel Connection Information
Connection | Panel |
RS232-T | 9 Way D-Type Pin 2 |
RS232-R | 9 Way D-Type Pin 3 |
RTN | 9 Way D-Type Pin 5 |
Panel Programming
Go to Menu 52 Digicom
- Select Comms Format
- Select ARC No <01234 567890>
- Select account no <_____> (Ignore accounts 2-8)
- Select dialing mode
- Select DigiCom options
- Select Restore signals
- Select FF Channels <8 FF Channels>
- Select Line fault
Go to Menu 53 – RS232 Options
- Select RS232 option baud <38400>
- Select Remote modem
- Go to Menu 51
- Select Serial Number <_____> (Site/Chip ID)
- Select Account Name <_____> (Site/Chip ID)
- Select Access mode
- Select Edit call Nos
- Select Modem Options rings to answer
- Select Baud Rate <1200>
- Select Downloader – Modem Options – Ans Phone Defeat
- Select Modem Options rings to answer
- Select Baud Rate <1200>
- Select Downloader – Modem Options – Ans Phone Defeat
Remote Access Programming
- Go to “Set Up Downloading”
- Select “Download” by (WebWayOne)
- Select “Poll Timeout” <10>
- Select “Modem Init Timeout” <060>
- Select “Rings To Answer” <1>
- Select “Comm. Tx Timeout” <030>
- Select “Program PCs” <1>
- Select “Signal Alarms” (No)
- Select “Signal Faults” (No)
- Select “Signal Set/Unset” (No)
- Select “Signal Access Code” (No)
- Select “Password” (optional UDL password)
- Select “Redials” <03>